26/35KV Heat shrink terminal and splices for crosslinked cable
We have more than 35 kinds of heat shrink material.
Please contact us, so that we can help you select the right product to meet your needs and fit your budget !
Product facts
- Applications:Suitable for power cables up to 35kv. - Test standard:JB 8144 IEC60
Application
Widely used in terminal treatment and intermediate splices of high-voltage cable.
Technical data
Items | Test item | Standard requirement | Test result | Conclusion |
35kv outdoor/indoor terminal and splices | Power frequency voltage withstand test | 105kv/min, no flash, no breakdown | 105kv/min, no flash, no breakdown | Qualified |
Partial discharge test | 39kv,≤20pc | 13kv, 2pc | Qualified |
Load circulation test (3 circulations) | 5h heated, 3h cooled, the temperature of conductor is 95℃ while heating | See below | |
Partial discharge test | 39kv,≤20pc | 39kv, 4pc | Qualified |
Impulse voltage test | 250kv, commit 10 times respectively on positive and negative pole, one flash is permitted, but will not be counted to the total test times | 250kv, no flash, no breakdown. | Qualified |
Negative pole direct voltage test | 156kv/15min, no flash, no breakdown | 156kv/15min, no flash, no breakdown | Qualified |
4hPower frequency voltage test | 104kv/4h, no flash, no breakdown | 104kv/4h, no flash, no breakdown | Qualified |
Specification
Product name | Models | Applicable cable section (mm2) |
35kv one-core indoor terminal | NRSY-35/1.1 | 50-95 |
NRSY-35/1.2 | 120-185 |
NRSY-35/1.3 | 240-400 |
NRSY-35/1.4 | 500-800 |
35kv one-core outdoor terminal | WRSY-35/1.1 | 50-95 |
WRSY-35/1.2 | 120-185 |
WRSY-35/1.3 | 240-400 |
WRSY-35/1.4 | 500-800 |
35kv three-core indoor terminal | NRSY-35/3.1 | 50-95 |
NRSY-35/3.2 | 120-185 |
NRSY-35/3.3 | 240-400 |
NRSY-35/3.4 | 500-800 |
35kv three-core outdoor terminal | WRSY-35/3.1 | 50-95 |
WRSY-35/3.2 | 120-185 |
WRSY-35/3.3 | 240-400 |
WRSY-35/3.4 | 500-800 |